Hochiki YBN-R/3(WHT)-OEM-SCI User Manual

Browse online or download User Manual for Audio accessories Hochiki YBN-R/3(WHT)-OEM-SCI. Hochiki YBN-R/3(WHT)-OEM-SCI User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 2
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
2-3-0-1591/ISS1/OCT12
HOCHIKI YBN-R/3(SCI)-OEM SHORT-CIRCUIT
ISOLATOR ADAPTOR INSTALLATION INSTRUCTIONS
General Description
The YBN-R/3(SCI)-OEM is an adaptor featuring an integral short-circuit isolator, which has
been designed to be fitted to a standard sensor mounting base (YBN-R/3) to convert it into a short-circuit isolator
base. This combined unit will then detect and isolate short-circuits on the loop. When a short-circuit is detected
the combined unit will drop the power to the rest of the loop.
The combined unit is compatible with the ESP range of sensors (see compatibility chart below) and does not
require a loop address. A remote fire LED facility is provided when a sensor is attached to the combined unit.
Note:- A fitted sensor will still be powered when this device is isolating.
Fitting to a YBN-R/3 Standard Base
Fit the adaptor to the underside of the YBN-R/3 standard mounting base as shown above, ensuring that the
alignment nibs on both units are aligned. The three fixing posts on the adaptor provide a snug fit to the moulded
posts on the underside of the YBN-R/3. Ensure that the flying leads on the adaptor are passed through the hole in
the base of the YBN-R/3.
Connect the two flying leads to the appropriate wiring terminals on the YBN-R/3. These are:
BLACK (Loop –ve) to terminal 6 and RED (Loop +ve) to terminal 1.
Compatibility
The combined unit as an isolator base has been designed to work with the sensors listed below. All sensors are
compatible with Hochiki ESP (Enhanced System Protocol).
Sensor Type Ordering Code
Photoelectric (smoke) sensor ALG-E, ALG-EN, ALK-E, ALN-E (and all variants)
Ionisation (smoke) sensor AIE-E (and all variants)
Temperature (heat) sensor ATG-E, ACB-E, ATJ-E (and all variants)
Multi (smoke and/or heat) sensor ACA-E, ACC-E (and all variants)
Page view 0
1 2

Summary of Contents

Page 1 - Sensor Type Ordering Code

2-3-0-1591/ISS1/OCT12 HOCHIKI YBN-R/3(SCI)-OEM SHORT-CIRCUIT ISOLATOR ADAPTOR INSTALLATION INSTRUCTIONS General Description The YBN-R/3(SCI)-OEM is a

Page 2 - 10% to 95% RH (at 40C)

2-3-0-1591/ISS1/OCT12 Specifications Ordering codes YBN-R/3(SCI)-OEM (ivory) YBN-R/3(WHT)-SCI-OEM (white) Protocol ESP Operating Voltage 19 - 41 V d

Related models: YBN-R/3(SCI)-OEM